The fire pump system, when started by pressure drop, should be arranged as follows:

(a) The jockey pump stop point should equal the pump churn pressure plus the minimum static supply pressure.
(b) The jockey pump start point should be at least 10 psi (0.68 bar) less than the jockey pump stop point.
(c) The fire pump start point should be 5 psi (0.34 bar) less than the jockey pump start point. Use 10 psi (0.68 bar) increments for each additional pump.
(d) Where minimum run times are provided, the pump will continue to operate after attaining these pressures.
The final pressures should not exceed the pressure rating of the system.
(e) Where the operating differential of pressure switches does not permit these settings, the settings
should be as close as equipment will permit. The settings should be established by pressures observed
on test gauges.


Examples of fire pump settings:

i. Pump: 1000 gpm, 100 psi pump with churn pressure of 115 psi
ii. Suction supply: 50 psi from city — minimum static; 60 psi from city — maximum static

iii. Jockey pump stop = 115 psi + 50 psi = 165 psi
iv. Jockey pump start = 165 psi - 10 psi = 155 psi
v. Fire pump stop = 115 psi + 50 psi = 165 psi
vi. Fire pump start = 155 psi - 5 psi = 150 psi
vii. Fire pump maximum churn = 115 psi + 60 psi = 175 psi

9 comments:

  1. Very helpful information. if possible please mention reference with chapter and points.

    ReplyDelete
  2. Very helpful information. if possible please mention reference with chapter and points.

    ReplyDelete
  3. It depends on architecture.
    Anyways informative.

    Regards,
    Nayab Zafar
    CEO
    Www.xclusive-solutions.com

    ReplyDelete
  4. Wallah no comments, you are great

    ReplyDelete
  5. some of the fire pump churn pressure is very high that kind of pump set we cant able to fix the same example. NFPA 20 does not mentioned Jockey pump selected based on the fire pump churn pressure.

    ReplyDelete
  6. most of the fire pump rated pressure more than 200 psi the shut of pressure will be more than 240 psi. this case how we set the jockey cut in cut out more than rated pressure. and some time selected jockey pump pressure its not meet the fire pump churn pressure. moreover as per NFPA 20 didn't say Jockey pump select based on the fire pump churn pressure.

    ReplyDelete